The C-10 guide applies to exams scheduled on or after June 1, 2024, and lists approximate section percentages. CSLB's Examination FAQ is the source for official exam details; CXP's Spanish-language practice is not a claim that CSLB offers the C-10 classification exam in Spanish. The 115-question mock is not an official exam length.
Exam topics and approximate weights: CSLB study guide.
What is the calculated continuous load feeder demand for a commercial branch circuit with a non-continuous load of 80 Amperes and a continuous load of 100 Amperes?
Correct answer: 205 Amperes
Explanation: Under the 2022 California Electrical Code (CEC), CCR Title 24, Part 3, §215.2(A)(1), adopting NEC §215.2(A)(1), continuous feeder loads are calculated at 125%: 100 A × 125% = 100 A × 1.25 = 125 A, and 80 A + 125 A = 205 A. Therefore, 205 Amperes is correct. 180 Amperes simply adds 80 A + 100 A without adjustment, 200 Amperes uses an unsupported 120% factor, and 225 Amperes applies an excessive factor. The governing rule is the CEC/NEC feeder-ampacity requirement, not CBC, OSHA, or contractor-licensing provisions.